EasyManua.ls Logo

Viessmann VITOPEND 200 - Checking the Static and Supply Pressure

Viessmann VITOPEND 200
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Checking the static and supply pressure
Danger
CO build-up as a result of an incorrect burner setup can have serious
health implications.
Carry out a CO test prior to and after work on gas equipment.
Operation with LPG
Flush the LPG tank twice during com-
missioning/replacement. Thoroughly
vent the tank and gas supply lines
after flushing.
1. Close the gas shut-off valve.
2. Undo the screw inside test connec-
tor A at the gas train, but do not
remove it, and connect the pres-
sure gauge.
3. Open the gas shut-off valve.
4. Measure the static pressure and
record it in the service report.
Set value: max. 57.5 mbar
5. Start the boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 s press "E RESET" to
reset the burner.
6. Check the supply (flow) pressure.
Set value:
&
Natural gas: 20 mbar
&
LPG: 50 mbar
Note
Use suitable test equipment with a
resolution of at least 0.1 mbar to
measure the supply pressure.
7. Record the actual value in the ser-
vice report.
Take the action shown in the table.
8. Switch OFF the system at the con-
trol unit (the boiler shuts down),
close the gas shut-off valve,
remove the pressure gauge and
close test connector A with the
screw.
Further details regarding the individual steps (cont.)
25
Commissioning, inspection, maintenance
5862 831 GB
Service

Table of Contents

Other manuals for Viessmann VITOPEND 200

Related product manuals