Viessmann VITOPEND 200 - Fault Codes

Viessmann VITOPEND 200
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault
code
on the
display
Const. Weath.-
comp.
System char-
acteristics
Cause Measures
28 X X Regulates
without flow
temperature
sensor (low
loss header)
System flow
temperature
sensor lead
broken
Check the low
loss header sen-
sor (see page 90)
30 X X Burner
blocked
Boiler water
temperature
sensor
shorted out
Check the boiler
water tempera-
ture sensor (see
page 90)
38 X X Burner
blocked
Boiler water
temperature
sensor lead
broken
Check the boiler
water tempera-
ture sensor (see
page 90)
40 X Mixer closes Heating cir-
cuit with
mixer M2
flow tem-
perature
sensor
shorted out
Check flow tem-
perature sensor
48 X Mixer closes Heating cir-
cuit with
mixer M2
flow tem-
perature
sensor lead
broken
Check flow tem-
perature sensor
50 X X No DHW heat-
ing
Comfort sen-
sor shorted
out
Check sensor
(see page 90)
51 X X No DHW heat-
ing
Outlet tem-
perature
sensor
shorted out
Check sensor
(see page 90)
58 X X No DHW heat-
ing
Comfort sen-
sor lead bro-
ken
Check sensor
(see page 90)
Fault codes (cont.)
81
Troubleshooting
5862 831 GB
Service