Checking the temperature limiter
Check the temperature limiter if the burner control unit cannot be reset after a
fault shutdown, although the boiler water temperature is below approx. 90 °C
(display "E").
A Temperature limiter
1. Pull the leads from the temperature
limiter.
2. Check the continuity of the tem-
perature limiter with a multimeter.
3. Remove the faulty temperature lim-
iter.
4. Coat the replacement temperature
limiter with heat conducting paste
and install it.
5. After commissioning, press reset
button "E RESET" at the control
unit.
Repairs (cont.)
93
Troubleshooting
5862 831 GB