15
Rated heating output kW 150 200 250 310 400 410 500 620
Flue gas parameters
*2
Temperature at boiler water
temp. 80 °C
■
at rated heating output °C 215
■
at partial load (60 %) °C 155
Product ID CE-0085BP0365
Efficiency η at
■
100 % of the rated heating
output (80/65 °C)
% 90.8 91.0 90.9 91.0 90.9 90.9 91.0 91.1
■
30 % of the rated heating
output (80/65 °C)
% 94.5 94.9 94.7 95.0 94.7 94.7 95.0 95.2
*2
Values for sizing the flue system to EN 13384 relative to 13 % CO
2
for fuel oil EL and 10 % CO
2
for natural gas.
Specification
5592 753 GB