8. Summary table of thermostat parameters
Function Parameters Value range Resolution Default value
Multi-function input IN selection
[Off, Nighttime
Reduction,
Activation,
Heating/Air-Con.]
- Off
External temperature probe
EXT Probe se
-
lection
[Off, View,
Temperature
Control,
Limitation]
- Off
Nighttime Reduction
δ
R (red. offset)
[1,..,6]°C 0.1°C 4°C
Limitation TL (Temp. limit) [30,..,50]°C 0.1°C 35°C
Temperature control mode
Selection
TempCtrl
[Heat., Air-con.] - Heating
Control algorithm Algorithm [ON/OFF, PID] - ON/OFF
Hysteresis (ON/OFF)
δ
T (Differential)
[0.1,..,1]°C 0.1°C 0.2°C
Proportional band (PID) Band [0.5,..,5]°C 0.1°C 1°C
Integral period (PID) Period [10,..,30] minutes 1 min 20 min
Unit of measurement (tem
-
perature)
Temperature unit [°C , °F] - °C
Temperature offset TE (Offset temp.) [0,..,±3]°C 0.1°C 0°C
PIN number Pin [000,..,999] 1 000
Temperature set-point
T
M (Man Heat.) [10,..,35]°C 0.1°C 18°C
T
M (Man Air-Con.) [10,..,35]°C 0.1°C 26°C
T
2 (Comfort Heat.) [10,..,35]°C 0.1°C 20°C
T
2 (Comfort Air-
Con.)
[10,..,35]°C 0.1°C 25°C
T
0 (No Heat.) [TG,10,..,35]°C 0.1°C 16°C
T
0 (No Air-Con.) [10,..,35,OFF]°C 0.1°C 29°C
T
G (Antifreeze) [4,..,10]°C 0.1°C 5°C
Table 1. Device parameters
9. Alarms
The thermostat is capable of displaying an alarm condition associated with the use of the external temperature
probe as described in subsection 7.6.