SW24.W
EN
LGC
L10
Step by step
Default
4
2 Step-step command operates in 2 steps: open, close, open...
3 Step-step command operates in 3 steps: open, stop, close, open...
4 Step-step command operates in 4 steps: open, stop, close, stop, open...
L11
Stop from step-step
Default
ON
OFF Automatic closing disabled when a stop command from step-step is given
ON Automatic closing not disabled when a stop command from step-step is given
L12
Stop from stop
Default
ON
OFF Automatic closing disabled when a stop command from stop is given
ON Automatic closing not disabled when a stop command from stop is given
L13
Hammering
Moves briey in the opposite direction to that of its travel to facilitate the release of the
electrical lock
Default
OFF
OFF Hammering o
1 On with gate closed
2 On with gate closed and open
3 On with gate open
L14
Operation in battery
Default
1
1 Standard operation
2 Normal operation with ashing light disabled
3 After a re-open command it stays open
4 When the main power supply is cut o it opens and remains open
L15
Economy
Default
OFF
OFF Standard operation
1
Economy operation on. With the gate closed, it switches o the accessory power supply on
outputs 1 and 2. The outputs are powered again following a new command.
L16
Gate blocked open indicator
Number of minutes after which, with the gate partially or totally open, whatever the set
pause time, an alarm signal is sent (on the display and output congured as OAB)
Default
30
OFF Indicator disabled
3 Minimum interval
60 Maximum interval