Manual VIPA System 200V Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44 3-35
… Continue
Alarm status at diagnostic alarm Bytes x+8 to x+19
(corresponds CPU diagnostic record set 1)
Byte Bit 7 ... Bit 0
x+8 70h: Module with digital inputs
71h: Module with analog inputs
72h: Module with digital outputs
73h: Module with analog outputs
74h: Module with analog in-/-outputs
76h: Counter
x+9 Lenght of the channel-specific diagnostic
x+10 Number of channels per module
x+12 Diagnostic event on the channel/channel group 0
Assignment see module description
x+13 Diagnostic event on the channel/channel group 1
Assignment see module description
.
.
.
.
.
.
x+19 Diagnostic event on the channel/channel group 7
Assignment see module description
Alarm status at process alarm Bytes x+4 to x+7
More detailed information to the diagnostic data is to find in the concerning
module descriptions.