Chapter 3 Deployment IM 253DP Manual VIPA System 200V
3-42 HB97E - IM - RE_253-xDPxx - Rev. 12/44
Note!
To connect this EasyConn plug, please use the standard PROFIBUS cable
type A (EN50170). Starting with release 5 you also can use highly flexible
bus cable: Lapp Kabel order no.: 2170222, 2170822, 2170322.
With the order no. 905-6AA00 VIPA offers the "EasyStrip" de-isolating tool
that makes the connection of the EasyConn much easier.
11 6
Dimensions in mm
The "EasyConn" bus connector is provided with a switch that is used to
activate a terminating resistor.
1./last
bus participant
further
participants
Attention!
The terminating resistor is only effec-
tive, if the connector is installed at a bus
participant and the bus participant is
connected to a power supply.
Note!
A complete description of installation
and deployment of the terminating
resistors is delivered with the connector.
Loosen the screw.
Lift contact-cover.
Insert both wires into the ducts
provided (watch for the correct
line color as below!)
Please take care not to cause a
short circuit between screen and
data lines!
Close the contact cover.
Tighten screw
(max. tightening torque 4Nm).
The green line must be connected to A, the red line to B!
Termination with
"EasyConn"
Wiring
Assembly
Please note: