Chapter 3 Deployment IM 253DP Manual VIPA System 200V
3-56 HB97E - IM - RE_253-xDPxx - Rev. 12/44
To be compatible with the STEP
7 projecting tool from Siemens, you have
to execute the following steps for CPU 214 and DP master:
• Start the Hardware configurator from Siemens
• Install the GSD-file vipa_21x.gsd
• Project a CPU 315-2DP with DP master (master address 2)
• Add a PROFIBUS slave "VIPA_CPU21x" with address 1.
• Include a CPU 214-1BA03 at slot 0 of the slave system
• Include the DP master 208-1DP01 (place holder) at slot 1 and include
the output module 222-1BF00 at slot 2.
• Give the output module 222-1BF00 at slot 0.
To connect your real CPU 214DP, you have to execute the following steps
after including the GSD-file vipa04d5.gsd:
• Add the PROFIBUS slave "VIPA_CPU2xxDP" (address 3)
• Include the "2 Byte Output" element at slot 0 and choose the output
address 20.
• Include the "2 Byte Input" element at slot 1 and choose the input
address 10.
• Save your project.
Engineering
CPU 214 of the
DP master
PROFIBUS link-up
of the CPU 214DP