Chapter 3 Deployment IM 253DP Manual VIPA System 200V
3-58 HB97E - IM - RE_253-xDPxx - Rev. 12/44
To be compatible with the Siemens SIMATIC Manager, you have to
execute the following steps for the CPU 214DP:
• Start the Hardware configurator from Siemens
• Install the GSD-file vipa_21x.gsd
• Project a CPU 315-2DP with DP master (master address 2)
• Add a PROFIBUS slave "VIPA_CPU21x" with address 1.
• Include the CPU 214-2BP03 at slot 0
• Select the following parameters for the CPU 214DP:
- Input Add.: 30
- Input Length: 2
- Output Add.: 40
- Output Length: 2
- Prm. Add.: 800
- Diag. Add.: 900
- Stat. Add.: 1020
- PROFIBUS DP Add.: 3
• Include the output module 222-1BF00 at slot 1 and give them the output
address 0.
• Safe your project.
Engineering
CPU 214DP