Chapter 4 CANopen Manual VIPA System 300V
4-38 HB130E - IM - Rev. 08/26
Index Sub-
index
Name Type Attr. Map. Default value Meaning
0x1800 0 Number of
Elements
Unsigned8 ro N 0x05 Communication parameter of
the first transmit PDO, sub-
index 0: number of following
parameters
1 COB-ID Unsigned32 rw N 0x80000180
+ NODE_ID
COB-ID TxPDO1
2
Transmission
type
Unsigned8 rw N 0xFF Transmission type of the PDO
3 Inhibit time Unsigned16 rw N 0x0000 Repetition delay
[value x 100 µs]
5 Event time Unsigned16 rw N 0x0000 Event timer [value x 1 ms]
Sub-index 1 (COB-ID): The lower 11Bit of the 32Bit value (Bits 0-10)
contain the CAN identifier, the MSBit (Bit 31) shows if the PDO is active (1)
or not (0), Bit 30 shows if a RTR access to this PDO is permitted (0) or not
(1). The sub-index 2 contains the transmission type, sub-index 3 the
repetition delay time between two equal PDOs. If an event timer exists with
a value unequal 0, the PDO is transmitted when the timer exceeds.
If a inhibit timer exists, the event is delayed for this time.
Index Sub-
index
Name Type Attr. Map. Default value Meaning
0x1801 0 Number of
Elements
Unsigned8 ro N 0x05 Communication parameter of
the second transmit PDO, sub-
index 0: number of following
parameters
1 COB-ID Unsigned32 rw N 0x80000280
+ NODE_ID
COB-ID TxPDO2
2
Transmission
type
Unsigned8 rw N 0xFF Transmission type of the PDO
3 Inhibit time Unsigned16 rw N 0x0000 Repetition delay
[value x 100 µs]
5 Event time Unsigned16 rw N 0x0000 Event timer [value x 1 ms]
Communication
parameter TxPDO1
Communication
parameter TxPDO2