Manual VIPA System 300V Chapter 4 CANopen
HB130E - IM - Rev. 08/26 4-61
Index Sub-
Index
Name Type Attr. Map. Default value Meaning
0x6443 0x00 Analog
output block
Unsigned8 ro N Depending on
the compo-
nents fitted
Number of available analog
outputs
0x01 1st analog
output block
Unsigned8 rw N 0xFF 1st error mode analog output
block
... ... ... ... ... ... ...
0x24 36th analog
output block
Unsigned8 rw N 0xFF 36th error mode analog output
block
This object indicates whether an output is set to a pre-defined error value
(set in object 0x6444) in case of an internal device failure.
0 = current value
1 = set to error value 0x6444
Index Sub-
Index
Name Type Attr. Map. Default value Meaning
0x6444 0x00 16bit digital
input block
Unsigned8 ro N Depending on
the compo-
nents fitted
Number of available analog
output blocks
0x01 1st analog
block
Unsigned16 rw N 0x0000 1st analog output block
... ... ... ... ... ... ...
0x24 36th analog
block
Unsigned16 rw N 0x0000 36th analog output block
Presupposed that the corresponding error (0x6443) is active, device
failures set the output to the value configured by this object.
Fault mode
analog output
Fault state
analog output