Chapter 3 Profibus DP Manual VIPA System 300V
3-20 HB130E - IM - Rev. 08/26
The module-related diagnostic shows the state of the projected modules
and details the identifier-related diagnostic concerning the configuration.
The length of the module-related diagnostic data is fixed at 12Byte.
Module status
Byte Bit 7 ... Bit 0
11 Bit 5 ... 0: Length module-related diagnostic data
001100: Length 12 Byte (fix)
Bit 7 ... 6: Code for module-related diagnostic
00: Code 00 (fix)
12 Bit 6 ... 0: Status type
0000010: Module state
Bit 7: 1 (fix)
13 permanent 00
14 permanent 00
15 Bit 1 ... 0: Module at plug-in location 1
Bit 3 ... 2: Module at plug-in location 2
Bit 5 ... 4: Module at plug-in location 3
Bit 7 ... 6: Module at plug-in location 4
16 Bit 1 ... 0: Module at plug-in location 5
.
.
.
Bit 7 ... 6: Module at plug-in location 8
17 Bit 1 ... 0: Module at plug-in location 9
.
.
.
Bit 7 ... 6: Module at plug-in location 12
18 Bit 1 ... 0: Module at plug-in location 13
.
.
.
Bit 7 ... 6: Module at plug-in location 16
19 Bit 1 ... 0: Module at plug-in location 17
.
.
.
Bit 7 ... 6: Module at plug-in location 20
20 Bit 1 ... 0: Module at plug-in location 21
.
.
.
Bit 7 ... 6: Module at plug-in location 24
21 Bit 1 ... 0: Module at plug-in location 25
.
.
.
Bit 7 ... 6: Module at plug-in location 28
22 Bit 1 ... 0: Module at plug-in location 29
.
.
.
Bit 7 ... 6: Module at plug-in location 32
Module-related
diagnostic data
IM 353-1DP00
The Bits in Byte
15 ... 22 may have the
following values:
00: Module OK;
valid data
01: Modul error;
invalid data
(Module defective)
10: wrong module;
invalid data
11: no module;
invalid data