If “User-Defined” is selected,
battery charge voltage and low DC
cut-off voltage can be set up in
program 26, 27 and 29.
Auto restart when overload
occurs
Restart disable (default)
Auto restart when over
temperature occurs
Restart disable (default)
Maximum utility charging
current
Note: If setting value in
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02 for
utility charger.
Setting range is 2A, then from 10A
to 100A. Increment of each click is
10A.
Setting voltage point back
to utility source when
selecting “SBU priority” in
program 01.
Available options in 3KVA model:
Setting range is from 22V to
25.5V. Increment of each click is
0.5V.
Available options in 5KVA model:
Setting range is from 44V to 51V.
Increment of each click is 1V.
Setting voltage point back
to battery mode when
selecting “SBU priority” in
program 01.
Available options in 3KVA model:
Setting range is from 24V to 29V. Increment of each click is 0.5V.
Available options in 5KVA model:
Setting range is from 48V to 58V. Increment of each click is 1V.