EasyManua.ls Logo

Voltronic Power 3KVA - Appendix: Approximate Back-up Time Table

Voltronic Power 3KVA
33 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
Appendix: Approximate Back-up Time Table
Model
Load (VA)
Backup Time @ 24Vdc 100Ah (min)
Backup Time @ 24Vdc 200Ah (min)
3KW
300
359
880
600
176
420
900
99.2
242
1200
76
182
1500
54
131
1800
45
101
2100
38
86
2400
28
75
2700
25
59
3000
22
54
Model
Load (VA)
Backup Time @ 48Vdc 100Ah (min)
Backup Time @ 48Vdc 200Ah (min)
5KW
500
490
1030
1000
214
490
1500
126
322
2000
89
217
2500
72
172
3000
61
146
3500
52
113
4000
40
90
4500
35
80
5000
32
72
Note: Backup time depends on the quality of the battery, age of battery and type of battery.