Setting range is from 25.0V to 31.5V for 3KVA model and 48.0V to
61.0V for 5KVA model. Increment of each click is 0.1V.
Setting range is from 5min to 900min.
Increment of each click is 5min.
Battery equalized timeout
Setting range is from 5min to 900 min.
Increment of each click is 5 min.
Setting range is from 0 to 90 days.
Increment of each click is 1 day
Equalization activated
immediately
If equalization function is enabled in program 30, this program can
be set up. If “Enable” is selected in this program, it’s to activate
battery equalization immediately and LCD main page will shows
“ ”. If “Disable” is selected, it will cancel equalization function
until next activated equalization time arrives based on program 35
setting. At this time, “ ” will not be shown in LCD main page.
Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging
power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in
Watt, DC discharging current, main CPU Version.
Input voltage/Output voltage
(Default Display Screen)
Input Voltage=230V, output voltage=230V