Chapter3 product appearance and wiring IR610 high performance vector control frequency inverter user manual
- 36 -
Inverter1 inverter2 inverter3
Invert1 Inverter2 inverter3
Correct incorrect
3-27-1 Ground wire connection diagram
Frequency converter to motor cable length and carrier frequency to maintain the appropriate
relationship
When the cable between the inverter and the motor is long, due to the influence of distributed capacitance, it is easy
to produce electrical resonance, thus generating a large current so that the inverter over-current protection. It is
recommended to install the AC output reactor when the motor cable length exceeds 100 meters. Refer to the
following table for carrier frequency setting
Inverter output cable length and carrier frequency table
3-27-2 diagram
Cable length between drive
and motor
20m below
50m below
100m below
100m above
Carrier frequencyP22.00
15kHz below
8kHz below
4kHz below
2kHzbelow