IR610 high performance vector control frequency inverter user manual Chapter 5 function code table
- 90 -
with loading.
Reduce this setting when the motor
speed is higher than the target value
with loading,
Slip compensation filter time
0.01s~10.00s
It is used to adjust the speed and stability of
the VF control response to the load.
Decrease this setting when the load
response is slow.
Increase this setting when the speed is
unstable
Oscillation suppression gains
0~2000
In the SVPWM control mode, current
fluctuation may occur to the motor on some
frequency, especially the motor with
big power. The motor can not run stably or
overcurrent may occur. These phenomena
can be canceled by adjusting thisparameter.
Oscillation suppression
effective frequency range
Oscillation suppression effective
range :100%~1200%
Set the range of the oscillation suppression
function, 100% corresponds to the rated
frequency of the motor
Current limit function
selection
0:ineffective
1:only adjust output voltage(Current limiting
for general VF separation)
2:adjust output frequency
20%~180% drive rated current
Weak magnetic zone current
limit factor
optimize dynamic performance of Weak
magnetic zone,10%~100%
Voltage source for VF
separation
0:digital setting
1:AI1
2:AI2