SmartPlate Installation, Operation & Maintenance Manual
APPENDIX A MODBUS CONTROL AND COMMUNICATION
OMM-0069_0H SP-100 1/30/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 98 of 134
A.1.2 Changing the Temperature Controller Communication Addresses
NOTE:
Refer to the button map at the bottom of the display, Figure A-4, for all panel navigation
instructions.
Figure A-4
The Temperature Controller address is defaulted to 1 from the factory. To change the MODBUS
address, proceed as follows:
1. Page to the ACCS list and Scroll
down to codE.
Page
Scroll
Down Arrow
Up Arrow
Button Map