Regulation type:
- HYs: regulation of hysteresis
- bP: regulation of proportional type
Factory setting value: bP Other values: HYs
Hysteresis value:
This menu is displayed only if parameter “typ” is equal to
“HYs”. Use
and keys to set hysteresis value. The setting
is validated with key .
Default value: 0.3°C Value range: 0.2°C to 3°C
Choice of concrete type:
Two choices are possible:
- uf1: for thin liquid concrete < 6 cm
- uf2: for traditional concrete with a thickness higher than 6 cm
if parameter #26 is set to “HYs” this menu is not available.
Factory setting value: uf1 Other values: uf2
Choice of coating:
Two choices are possible:
- bP1: for tiling
- bP2: for wooden floors (floating or not)
if parameter #26 is set to “HYs” this menu is not available.
Factory setting value: bP1 Other values: bP2
Function of pilot wire:
This option is used to enable the pilot wire functionality if it’s
used on your installation.
Factory setting value: no Other values: yes
Minimum value of setting range of the set point
temperature:
Factory setting value: 5.0°C Other values: 5.0°C to 15.0°C
Maximum value of setting range of the set point
temperature:
Factory setting value: 37.0°C Other values: 20.0°C to 37.0°C
Humidity set point (Optional)
Factory setting value: 75 % Other values: 0% (“no”) to 100%