HSG
SERIES
WITH A HONEYWELL
S89E, S89F
PRIMARY
IGNITION
CONTROLS
TROUBLE
SHOOTING GUIDE
MOTOR DOES
NOT
START
Replace
24
volt
AC
20
VA
Transformer
2. Check
tor
24
volts AC between
terminals
1
and
3
on
motor
start
relay.
3. Check
for 120
volts
AC between terminal 2 on
motorstart
relay
and
neutral line.
4.
Check electrical
wiring
and connections.
1.
Check
for
blower
clearance.
2. Lubricate motor
bearings.
5.
Does motor
shaft
turn
freely?
Check
the
low voltage transformer tor 24
volt
output
between
terminal
3
on the motor start
relay
either
of the'T'terminals
on the control box.
IGNITION
ARC ESTABLISHED
-
NO FLAME
l.
Reset
Control
-
Motor starts
-
Completes 30 second
prepurge
cycle, 8
second
safe start check
and
trial for
ignition,
4
seconds Honeywell series.
NOTE:
The burner motor
will
continue
to
operate
during
the lock
out
mode when
the thermostat circuit
is
called for burner operation.
2. Check
for
correct orifice/air setting
relationship
(see
figures 10,
12A,
128,
and 12C).
In
order for the following functional test to be made,
the control
must
be reset and
the
tests
monitored
dur-
ing
the
4
second
Honeywell
series trial
for ignition
peri-
od
that
occurs
at
the END of the 30 second
prepurge
and
I
second safe
start
check
cycle.
3. Check tor 24 volts AC at
gas
valve
terminals.
Check
electrical
wiring
and
connections.
Be sure leads
are on
correct
gas
valve ter-
minals
4. Make
sure
leads
are on the correct
gas
valve
terminals
pressure
PAGE
12
HSG SERIES WITH A HONEYWELL S89E, S89F PRIMARY IGNITION CONTROLS
TROUBLE SHOOTING GUIDE
MOTOR DOES
NOT
START
I.
Check the low voltage transformer for
24
volt output
between terminal 3 on the motor start relay either
of
the
"T'
terminals
on
the control box.
2.
Check for
24
volts AC between terminals 1 and 3
on
motor start relay.
3.
Check for 120 volts AC between terminal 2 on
motorstart relay and neutral line.
4.
Check electrical wiring and connections.
Check electrical wiring and
connections.
Check electrical wiring and
connections.
Check electrical wiring and
connections.
Replace
24
volt
AC
20
VA
Transformer
Replace motor
start relay.
Replace motor
start relay.
5.
Does motor shaft turn freely?
6.
IGNITION ARC ESTABLISHED -
NO
FLAME
OK
1.
Check for blower clearance.
2.
Lubricate motor bearings.
Reset Control - Motor starts - Completes 30 second prepurge cycle, 8 second safe start check and trial for
ignition, 4 seconds Honeywell series. NOTE: The burner motor will continue
to
operate during the lock out mode when the thermostat circuit
is
called for burner operation.
2.
Check for correct orifice/air setting relationship (see figures
10,
12A, 12B, and 12C).
In
order for the following functional test to be made,
the control
must
be reset and the tests monitored dur-
ing
the 4 second Honeywell series trial for ignition peri-
od
that occurs at the END of the 30 second prepurge
and
8 second safe start check cycle.
3.
Check for
24
volts AC at gas valve terminals.
4.
Make sure leads are on the correct gas valve
terminals
Check for correct manifold regulated pressure
(see figure 10).
Check electrical wiring and
connections.
Be
sure leads
are
on
correct gas valve ter-
minals
Replace primary
ignition control.
6.
PAGE 12