WECON VM AC Drive User Manual V2.0
WECON technology Co., Ltd
- 8 -
Code
Name
Range
Default
Feature
RAM
address
F0.03
Main Frequency
Source X option
0: F0.08
1: Keypad Potentiometer
2: AI1
3: Reserved
4: DI Terminal UP/DW
5: Reserved
6: Multi-Stage Speed
7: Inner Simple PLC
8: PID Control
9: RS485
Communication(Including
External Keypad)
1
0003
F0.04
Auxiliary
Frequency Source Y
option
Same as F0.03
0
0004
F0.05
Range of Auxiliary
Frequency Source Y
0: Relative to F0.10
1: Relative to Main
Frequency Source X (F0.03)
0
0005
F0.06
Percentage Range of
Auxiliary
Frequency Source Y
0% to 150%
100%
0006
F0.07
Combination Option of
F0.03 & F0.04
LED Ones Place: Frequency
Source Selection
0: Main Frequency Source
1: Main and Auxiliary
Operation Results
2: Switchover between
Main and Auxiliary
3: Switchover between X
and Main (X) & Auxiliary (Y)
Operation
4: Switchover between Y
and Main (X) & Auxiliary (Y)
Operation
LED Tens Place:
Combination Operation
0: Main Auxiliary
1: MainAuxiliary
2: MAX {Main, Auxiliary}
3: MIN {Main, Auxiliary}
4: Main * Auxiliary
LED Hundreds Place:
Reserved
0
0007
F0.08
Keypad Setting
Frequency
0.00 to F0.12
50.00Hz
0008