WECON VM AC Drive User Manual V2.0
WECON technology Co., Ltd
- 9 -
Code
Name
Range
Default
Feature
RAM
address
F0.09
Running Direction
0: FWD
1: REV
2: REV Forbidden
0
0009
F0.10
Maximum Output
Frequency
0.00 to 320.00Hz
50.00Hz
000A
F0.11
Upper Limit Frequency
Source
0: F0.12
1: AI1
2: Reserved
3: Reserved
4: Reserved
5: RS485 Communication
6: Reserved
7: Keypad Potentiometer
0
000B
F0.12
Maximum Running
Frequency
F0.14 to F0.10
50.00Hz
000C
F0.13
Reserved
Reserved
0.00Hz
000D
F0.14
Lower Limit Frequency
0.00 to F0.12
0.00Hz
000E
F0.15
The Function of
Frequency
Lower Limit
0: Stop
1: Run at Lower Limit
Frequency
2: Run at 0 Speed
1
000F
F0.16
Carrier Frequency
0.6 to 15.0kHz
Due to
VFD Model
0010
F0.17
Reserved
Reserved
1001
0011
F0.18
Acceleration Time 1
0.01 to 650.00s
Due to
VFD Model
0012
F0.19
Deceleration Time 1
0.01 to 650.00s
Due to
VFD Model
0013
F0.20
Default Setting
Restoring
0: No Option
1: Recover Default Settings
(Except F2 Team)
2: Clear All Error Records
3: Recover Default Settings
(Including F2 Team)
0
0014
F0.21
Parameter Lock
0: Invalid (Unlock)
1: Valid(Lock)
0
0015
F0.23
Unit of Acceleration &
Deceleration Time
0: 1Sec
1: 0.1Sec
2: 0.01Sec
2
0017
F0.24
Acceleration And
Deceleration Time
Reference Frequency
0: F0.10
1: F0.08
2: 100Hz
0
0018