Outputs
Relay Output
Safe Area Zone 2 Installation
Voltage max. 250 V AC / 30 V 32 V AC / 30 V DC
Power max. 500 VA / 60 W 16 VA / 60 W
Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC
Transistor/NPN Outputs
Max. switch frequency 5 kHz
Min. pulse length 60 μs
Max. load, current/voltage 80 mA/30 V DC
Voltage drop at 80 mA < 2.5 V DC
Status Relay Output
Safe Area Zone 2 Installation
Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC
Common Specifications
Supply voltage 19.2…31.2 V DC
NAMUR supply 8 V DC / 8 mA
Max. consumption 3 W (2 channels)
Fuse 400 mA / 250 V AC
Isolation Voltages, Test/Operation
Inputs/outputs/supply 2.6 kV AC / 300 V AC reinforced
Output 1 to output 2 1.5 kV AC / 150 V AC reinforced
Status relay to supply 1.5 kV AC / 150 V AC reinforced
Response time for cable fault < 200 ms