7.2.4 Specifications
Features
Configuration and monitoring are performed via FDT/DTM Software ‘WI-Manager’ (process calibration,
signal simulation).
Inputs for RTD, TC and mA signals, one or two full separated channels with active or passive inputs.
TC inputs can use either the internal CJC or a terminal with a built-in Pt100 Sensor ACT20X-CJC-HTI
(order No. 116064, channel 1 / order No. 116065, channel 2) for higher accuracy.
The two-channel version is suitable to use as a signal splitter.
The device automatically detects whether it is connected to an active or a passive current signal.
One green and two red front LEDs indicate operation status and malfunction.
2.6 kVAC galvanic isolation between input, output and supply
The device can be mounted in the safe area and in zone 2 / div. 2 and receive signals from zone 0, 1, 2,
20, 21 and 22 / Class I / II / III, Div. 1, Gr. A-G.