7.4.4 Specifications
Features
Configuration and monitoring are performed via FDT/DTM Software ‘WI-Manager’ (process calibration,
signal simulation).
Inputs for RTD, TC, Ohm, potentiometer, mA and V.
Power supply and signal isolator for 2-wire transmitters.
The input of the ACT20X-HUI-SAO can receive active and passive current signals.
Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
Reduced U
0
Ex data < 8.3 V for active input
signals (see Ex data in appendix).
TC inputs can use either the internal CJC or a terminal with a built-in Pt100 Sensor ACT20X-CJC-HTI
(order No. 116064, channel 1 / order No. 116065, channel 2) for higher accuracy.
The device automatically detects whether it is connected to an active or a passive current signal.
One green and one red front LEDs indicate operation status and malfunction. One yellow LED indicates
the relay status.
2.6 kVAC galvanic isolation between input, output and supply
The device can be mounted in the safe area and in zone 2 / div. 2 and receive signals from zones 0, 1, 2,
20, 21 and 22 / Class I/II/III, Div. 1, Gr. A-G.