7.3.4 Specifications
Features
Solenoid/alarm driver for the control of solenoids, acoustic alarms and LEDs installed in the hazardous
area
Two hardware versions make it possible to choose either low (35 mA) or high (50 mA) current output with
1-channel or 2-channel versions
Configuration via FDT/DTM Software ‘WI-Manager’. Selection of direct or inverted function for each
channel and the possibility of reducing the output current to the hazardous area to suit the application
The module can be mounted in the safe area and in zone 2/div. 2 and receive signals from zone 0, 1, 20,
21 and 22/Class I/II/III, Div. 1, Gr. A-G
Extended self diagnostic: Monitoring of error events via the individual status relay
LED indication: green and 2 yellow/red front LEDs to indicate operation status and malfunction
3-way galvanic isolation between input, output and supply, 2.6 kV AC