1066540000/00/02.09
53
Relay Parameters
Function SETPOINT
Contact function Normal Open
Setpoint 50 °C (input type temperature) / 50 %
Activation direction Increasing
Hysteresis 1 °C (input type temperature) / 1 %
Action on error Relay OPEN
Activation delay [s] 0
Deactivation delay [s] 0
Hysteresis
Setpoint high
ON delay OFF delay
Relay On Relay On
Closed
Open
Relay contact (N.O.)
Time
Window
ON delay OFF- delay
Hysteresis
Setpoint low
Illustration 7-13: Graphic depiction of window
Relay On
OFF delay
ON delay
Input
signal
Hysteresis
Setpoint
(increasing)
Time
Closed
Open
Relay contact
(N.O.)
Illustration 7-14: Graphic depiction of setpoint