EasyManua.ls Logo

Williamson Series 2 - Page 11

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Part Number 550-142-785/0812
GWI
Series 2 Gas-Fired Water Boilers – Boiler Manual
Direct exhaust venting continued
1. Donotmixtypesormanufacturersofventmaterials.
Useonlytheventstarterofthesamemanufacturer
astheventcomponents.Donotmixcomponents
fromdifferentsystems.Theventsystemcouldfail,
causing flue gas spillage, resulting in severe per-
sonal injury or death.
2. Clean all joints beforesealing.Seevent manufacturer’sin-
structionsforcleaningandsealingjoints.Usetheirspecied
sealant. Do not use screws.
3. Install ventpipewithseamsontop ofventhorizontalruns.
Followrequirementsonpage 10forventterminationlocation.
4. Maintainminimum2”clearancefromcombustiblematerials
to vent pipe.
5. Vertical venting — See Figure 6.Followventmanufacturer’s
instructionsforventingthroughroof.
• Vent pipe must extend through roof ashing, jacket or
thimble.
• Vent may pass through oor, inside wall or concealed
space when installed according to vent manufacturer’s
instructions.
Sidewall venting — See Figures 7 and 8. Vent must terminate
atleastone footaboveanticipatedsnowline.Vent mustbe
terminated only with:
• Elbowwithintegralscreen.
• Elbowandterminationcouplingwithscreen(notavailable
forStaR-34).
6. Donotsealventpipe(slipconnectorforSaf-TVent)toinside
or outside plate.
7. Ifpassingthroughnoncombustiblewall,provideholediam-
eterlargeenoughtoinserttheventpipe(slipconnectorfor
Saf-TVent).
8. Installhorizontaldrainteeascloseaspossibletoboiler,in
first horizontal run. See Figure 7.
9. Do not exceed the maximum vent system length givenin
Table 4, page 9.
Condensatedrainline—useonlysiliconetubing
ratedforatleast400°Ffortherst18”ofconden-
sate drain line, then other non-metallic tubing may
beused.Usinganyothermaterialcouldcauseue
gasleakage,potentiallyresultinginseverepersonal
injury, death or substantial property damage.
On some installations, the condensate drain fitting
may be omitted, provided:
• Ventmanufacturershowsthisoptionintheirinstruc-
tions.
• Ventisslopedtowardterminationasshownindotted
lines in Figure 7.
• Theventisinstalledperboilermanufacturer’sand
ventmanufacturer’sinstructions.
Condensatedrippagefromsuchventsmayaccumulateonthe
groundbelow.Considertrafcintheareatoavoidhazarddueto
ice accumulation.
Installing direct exhaust vent and termination
3 Vent installation continued
Figure 6 Vertical direct exhaust installation Figure 7 Direct exhaust through side wall