EasyManua.ls Logo

Williamson Series 2 - Air Openings

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
Part Number 550-142-785/0812
GWI
Series 2 Gas-Fired Water Boilers – Boiler Manual
Products to avoid
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinatedwaxes/cleaners
Chlorine-basedswimmingpoolchemicals
Calciumchlorideusedforthawing
Sodiumchlorideusedforwatersoftening
Refrigerantleaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cementsandglues
Antistaticfabricsoftenersusedinclothesdryers
Chlorine-typebleaches,detergents,andcleaningsolvents
foundinhouseholdlaundryrooms
Adhesivesusedtofastenbuildingproductsandothersimilar
products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metalfabricationplants
Beauty shops
Refrigerationrepairshops
Photo processing plants
Autobodyshops
Plasticmanufacturingplants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garageswithworkshops
Table 2 Corrosive contaminants and likely locations
To prevent potential of severepersonal injury or
death, checkfor products or areas listed below
beforeinstallingboiler.Ifanyofthesecontaminants
arefound:
• removecontaminantspermanently.
— OR —
• isolateboilerandprovideoutside combustionair.
Seenational,provincialor local codes forfurther
information.
Pleasereviewthefollowinginformationonpotentialcombustion
air contamination problems.
See Table 2forproductsandareaswhichmaycausecontami-
nated combustion air.
Air contamination Air openings
1 Prepare boiler location continued
CombustionairandventilationopeningsmustcomplywithSec-
tion 5.3,“Air for CombustionandVentilation”, of National Fuel
GasCodeANSIZ223.1–latestedition,orapplicablelocalbuilding
codes.CanadianinstallationsmustcomplywithB149.1orB149.2
InstallationCodes.
Seetablebelowforminimumcombustion/ventilationairopening
sizes.Whereopeningsarerequired,providetwo(2)openings—
onewithin12inchesoftheceiling,theotherwithin12inchesof
the floor, as shown in the table illustrations.
Provideadequatecombustionandventilationairto
assureproper combustionand reduce therisk of
severe personal injury, death or substantial property
damage caused by flue gas spillage and carbon
monoxideemissions.