EasyManua.ls Logo

Williamson Series 2 - Install Water Piping

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Part Number 550-142-785/0812
Table 6 Water pipe size (based on 20 °F rise)
General
Boiler
model
number
To
system
From
system
GWI-047
¾” ¾”
GWI-063
1” 1”
GWI-095
1” 1”
GWI-127
1” 1”
GWI-158
1 ¼” 1 ¼”
GWI-190
1 ¼” 1 ¼”
GWI
Series 2 Gas-Fired Water Boilers – Boiler Manual
IfinstallationistocomplywithASMEorCanadianrequirements,
anadditionalhightemperaturelimitisneeded.Installcontrolin
supply piping between boiler and isolation valve. Set second
controltominimum20°Fabovesetpointofrstcontrol.Maximum
allowablesetpointis240°F.Seepage 24 and 25forwiring.
Alowwatercutoffdeviceisrequiredwhenboilerisinstalledabove
radiation level or by certain state or local codes or insurance
companies.Uselowwatercutoffdesignedforwaterinstallations.
Electrodeprobe-typeisrecommended.Purchaseandinstall in
tee in supply piping above boiler.
Usebackowcheckvalveincoldwatersupplyifrequiredby
local codes.
See Figure 9(diaphragm-typeorbladder-typeexpansiontank)
orFigure10(closed-typeexpansiontank)onpage 14, and Table
6, fornear-boiler and single-zone systems designed for return
wateratleast130°F.
See page 13formultiple-zonepiping.
See page 14forboilersusedwithrefrigerationsystems.
Near-boiler piping
Relief valve
Installreliefvalveverticallyin¾”tappingonsideofboiler.See
thetagattachedtothereliefvalveformanufacturer’sinstructions.
To avoid water damage or scalding due to valve
operation, discharge line must be connected to re-
liefvalveoutletandruntoasafeplaceofdisposal.
Terminate the discharge line to eliminate possibility
ofsevereburnsshouldthevalvedischarge.
• Dischargelinemustbeasshortaspossibleandbe
the same size as the valve discharge connection
throughout its entire length.
• Dischargelinemustpitchdownwardfromthevalve
and terminate at least 6” above the floor drain where
any discharge will be clearly visible.
• Thedischargelineshallterminateplain,notthread-
ed,withamaterialserviceablefortemperaturesof
375°Forgreater.
• Donotpipethedischargetoanyplacewherefreez-
ing could occur.
• Noshutoffvalveshallbeinstalledbetweentherelief
valve and boiler, or in the discharge line. Do not plug
or place any obstruction in the discharge line.
• Failuretocomplywiththeaboveguidelinescould
resultinfailureofthereliefvalvetooperate,result-
inginpossibilityofseverepersonalinjury,deathor
substantial property damage.
• Testtheoperationofthevalveafterllingandpres-
surizingsystembyliftingthelever.Makesurethe
valvedischargesfreely.Ifthevalvefailstooperate
correctly,replaceitwithanewreliefvalve.
Circulator
The circulator is shipped loose (wiring pre-attached to boiler)
to allow you to locate it either in the return or supply piping, as
desired. See page 14foratypicalinstallation.Pipetheexpansion
tanktothesuctionsideofthecirculatorwheneverpossible.Install
anairseparatorinthesupplypiping.Connecttheexpansiontank
totheairseparatoronlyiftheseparatorisonthesuctionsideof
thecirculator.Alwaysinstallthesystemllconnectionatthesame
pointastheexpansiontankconnectiontothesystem.Figures 4
and 5 show typical near-boiler piping connections.
Expansion tank
Diaphragm- or bladder-type expansion tank — Figure 9,
page 14
1. Ensure expansion tank size will handle boiler and system
watervolumeandtemperature.Tankmustbelocatedinboiler
returnpipingasclosetoboileraspossible,beforeinletside
ofcirculator.Seetankmanufacturer’sinstructionsfordetails.
2. Installanautomaticairventasshown.
Closed-type expansion tank — Figure 10, page 14
1. Ensureexpansiontanksizewillhandleboilerandsystemwater
volumeandtemperature.Seetankmanufacturer’sinstructions
fordetails.
2. Connecttankto½”NPTtappinglocatedbehindsupplyoutlet,
using ½” NPT piping. Pitch any horizontal piping up towards
tank1inchper5feetofpiping.
Undersizedexpansion tanks cause system water
tobelostfromreliefvalveandmakeupwatertobe
addedthroughllvalve.Eventualsectionfailurecan
result.
Water piping — multiple zone systems
Installsystempipingusingeithercirculatorzoningorzonevalve
zoning.Installexpansiontankonsuctionsideofsystempump.
Alwaysconnectlllineonlyattheexpansion tank — neverat
another point in the system.
DO NOT connect directly from 3-wire zone
valves to the T-T terminals on the boiler
.
When using 3-wire zone valves, install an isolation
relay.Connectthezonevalveendswitchwiresto
theisolationrelaycoil.Connecttheisolationrelay
contact across the boiler T-T terminals. Failure to
comply can result in damage to boiler components
or cause unreliable operation, resulting in severe
property damage.
4 Install water piping4 Install water piping