Series 2 Gas-Fired Water Boilers – Boiler Manual
Water piping — refrigeration systems
Prevent chilled water from entering boiler
Installboilersothatchilledmediumispipedinparallelwiththe
heatingboiler.Useappropriatevalvestopreventchilledmedium
from entering boiler. See Figure 11 for typical installation of
balancingvalveandcheckvalve.
Figure 9 Diaphragm- or bladder-type expansion tank:
Piping to single-zone system using
diaphragm-type or bladder-type expansion
tank. See Table 6, page 13, for piping sizes.
Figure 10 Closed-type expansion tank: Piping to single-
zone system using closed-type expansion
tank. See Table 6, page 13, for piping sizes.
Figure 11 Piping refrigeration systems
Installboilersothatchilledmediumispipedinpar-
allelwithheatingboiler.Useappropriatevalvesto
preventchilledmediumfromenteringboiler.Consult
AHRIInstallationandPipingGuides.
If boiler is connected to heating coils located in
air handling units where they can be exposedto
refrigeratedair,useowcontrolvalvesorotherau-
tomatic means to prevent gravity circulation during
coolingcycle.Circulationofcoldwaterthroughthe
boilercouldresultindamagetotheheatexchanger,
causing possible severe personal injury, death or
substantial property damage.
Ifsystemincludesradiantheatingcircuits,provide
piping and controls to regulate the temperature sup-
plying the radiant circuits. Failure to comply could
result in substantial property damage.
UseFigure9orFigure10onlyforsystemsdesigned
forreturnwateratleast130°F.Forsystems with
low return water temperature, such as converted
gravity systems and radiant heating systems, install
bypasspiping(seepage 15)toprotectboileragainst
condensation. Failure to prevent low return water
temperaturetotheboilercouldcausecorrosionof
the boiler sections or burners, resulting in severe
personal injury, death or substantial property dam-
age.
4 Install water piping continued