EasyManua.ls Logo

Williamson Series 2 - Troubleshooting

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
Part Number 550-142-785/0812
GWI
Series 2 Gas-Fired Water Boilers – Boiler Manual
12 Troubleshooting
Labelallwirespriortodisconnectionwhenservic-
ing controls. Wiring errors can cause improper and
dangerous operation.
Neverjumper(bypass)rolloutthermalfuseelement
oranyotherdeviceexceptformomentarytestingas
outlinedin“Troubleshooting”charts,pages 34 - 40.
Severe personal injury, death or substantial property
damage can result.
Burner access panel must be in position during
boiler operation to prevent momentary flame rollout
onignitionofmainame.Severepersonalinjuryor
substantial property damage will result.
Before troubleshooting:
1. Havethefollowingitems:
a. Voltmeterthatcancheck120VACand24VAC.
b. Microammeterwithaminimumscalerangeof0-25.
c. Continuitychecker.
d. U-tubemanometer
e. Inclinedmanometerwith0–2”w.c.range.
2. Checkfor120VAC(minimum102VACtomaximum132VAC)
to boiler.
3. Makesurethermostatiscallingforheatandcontacts(includ-
ingappropriatezonecontrols)areclosed.Checkfor24VAC
between thermostat wire nuts and ground.
Check the following:
1. Wire connectors to control module are securely plugged in at
module and originating control.
2. Gaspressures(connectU-tubemanometeratgasvalvetap-
pings):
a. Withboileroff—13”w.c.maximumnaturalorpropane
gaspressureupstreamofgasvalve.
b. With boiler on:
• 5”w.c.minimumnaturalgaspressureor11”w.c.propane
gaspressureupstreamofgasvalve.
• 3.5”w.c.minimumnaturalgaspressureor10”w.c.propane
gaspressuredownstreamtappingongasvalve—Can
be adjusted by regulator on gas valve.
How to check pressure switch setting (if specified
in Troubleshooting charts
)
Make sure boiler water temperature is 100 °F or
coolerbeforestartingproceduretoobtainappropri-
ate readings.
1. See Figure 21 and Table 9.
2. Removeboth air pressure switchhoses from air pressure
switch.
3. Install tees and tubing as shown in Figure 21 to inclined
manometer.
4. Turnoffgasvalveandsetthermostattocallforheat.Inducer
will run but burners will not ignite.
5. Checkfor24VACbetweenbothairpressureswitchterminals.
6. Ifmanometerreadingisabovethesetpointoftheswitch(see
Table 9),butthereisnot24VACbetweenairpressureswitch
terminals“C”and“NO”—replaceairpressureswitch.
Troubleshooting air pressure reading
1. Ifmanometerreadingislowerthanthesetpointoftheswitch
(seeTable 9)—checkforpossiblecauses:
• blockageinhoses
• obstructionininducerhousingoutlet
• looseinducerwheelonmotorshaft
• inducermotornotinproperrpm
• inducerbackplatenotsealedproperly
• blockageinblockassembly
• blockageinuepipeortermination
• incorrectpressureswitch
Return to normal operation
When pressure reading is correct and air pressure switch is
operating properly — remove tees and reinstall hoses to air
pressure switch.
The boiler will not operate correctly unless pressure
switch hoses are correctly located. The red hose
connectsfromtherightside(negative)hosebarb
totheuecollector.Thewhitehoseconnectsfrom
theleftside(positive)hosebarboftheswitchtothe
connectorbox(betweenuecollectorandinducer)
as shown in Figure 21.
Table 9 Pressure switch setpoint (for elevations
above 2,000 ft, contact your local supplier for
details.)
Boiler model number Inches W.C.
GWI-047 and GWI-063
1.19
GWI-095
1.08
GWI-127
0.86
GWI-158
0.61
GWI-190
0.76
Figure 21 Checking pressure switch