Williamson Series 2 - Prepare Boiler Location; Series

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Part Number 550-142-785/0812
GWI
Series 2 Gas-Fired Water Boilers – Boiler Manual
Installations must follow these codes:
• Local,state,provincial,andnationalcodes,laws,regulations
and ordinances.
• NationalFuelGasCode,ANSIZ223.1–latestedition.
• StandardforControlsandSafetyDevicesforAutomatically
FiredBoilers,ANSI/ASMECSD-1,whenrequired.
• NationalElectricalCode.
• ForCanadaonly:B149.1orB149.2InstallationCode,CSA
C22.1CanadianElectricalCodePart1andanylocalcodes.
Certification
TheGWIboilergasmanifoldandcontrolsmetsafe
lightingandotherperformancecriteriawhenboiler
underwent tests specied in ANSI Z21.13–latest
edition.
Before locating the boiler:
Checkfornearbyconnectionto:
• Systemwaterpiping
• Ventingconnections
• Gassupplypiping
• Electricalpower
Checkareaaroundboiler.Removeanycombustiblematerials,
gasolineandotherammableliquids.
Failuretokeepboilerareaclearandfreeofcom-
bustible materials, gasoline and other flammable
liquids and vapors can result in severe personal
injury, death or substantial property damage.
Boiler must be installed so that gas control system components
areprotectedfromdrippingorsprayingwaterorrainduring
operation or service.
Ifnewboilerwillreplaceexistingboiler,checkforandcorrect
system problems, such as:
1. Systemleakscausingoxygencorrosionorsectioncracks
fromhardwaterdeposits.
2. Incorrectly-sizedexpansiontank.
3. Lackofantifreeze(whenrequired)inboilerwatercausing
systemandboilertofreezeandleak.
Failure to adhere to the guidelines below can
result in severe personal injury, death or sub-
stantial property damage.
When servicing boiler —
1. To avoidelectric shock, disconnect electrical supply
beforeperformingmaintenance.
2. Toavoidsevereburns,allowboilertocoolbeforeper-
formingmaintenance.
Boiler operation —
3. Donotblockowofcombustionorventilationairtoboiler.
4. Shouldoverheatingoccurorgassupplyfailtoshutoff,do
notturnoffordisconnectelectricalsupplytocirculator.
Instead,shutoffthegassupplyatalocationexternalto
the appliance.
5. Donotusethisboilerifanyparthasbeenunderwater.
Immediatelycallaqualiedservicetechniciantoinspect
theboilerandtoreplaceanypartofthecontrolsystem
and any gas control that has been under water.
Boiler water —
6. DO NOT use petroleum-based cleaning or sealing com-
pounds in boiler system. Water seal deterioration will oc-
cur,causingleakagebetweenboilersections,circulator
anges,diaphragmtanksorothersystemcomponents.
This can result in substantial property damage.
7. DO NOT use“homemade cures” or“boiler patent
medicines”. Serious damage to boiler, personnel and/
or property may result.
8. Continualfreshmakeupwaterwillreduceboilerlife.Min-
eralbuildupinsectionsreducesheattransfer,overheats
castiron,andcausessectionfailure.Additionofoxygen
and other gases can cause internal corrosion. Leaks
in boiler or piping must be repaired at once to prevent
makeupwater.
9. Donotaddcoldwatertohotboiler.Thermalshockcan
causesectionstocrack.
Glycol — potential fire hazard —
Allglycolisammablewhenexposedtohightemperatures.If
glycol is allowed to accumulate in or around the boiler or any
otherpotentialignitionsource,arecandevelop.Inorderto
prevent potential severe personal injury, death or substantial
propertydamagefromreand/orstructuraldamage:
• Never store glycol of any kind near the boiler or any
potential ignition source.
• Monitorandinspectthesystemandboilerregularlyfor
leakage.Repairanyleaksimmediatelytopreventpos-
sibleaccumulationofglycol.
• Neveruseautomotiveantifreezeor ethyleneglycolin
thesystem.Usingtheseglycolscanleadtohazardous
leakageofglycolintheboilersystem.
1 Prepare boiler locationRead this first!
Codes & checklist
The boiler contains ceramic fiber and fiber-
glassmaterials.Usecarewhenhandlingthese
materials per instructions on page 48ofthis
manual. Failure to comply could result in severe
personal injury.