Series 2 Gas-Fired Water Boilers – Boiler Manual
11 Service and maintenance continued
Theboilercontainsceramicberandberglassmaterials.Usecarewhenhandlingthesematerialsperinstructionson
page 48ofthismanual.Failuretocomplycouldresultinseverepersonalinjury.
❏ Inspect ❏ Inspect
Reported problems
Inspect anyproblems reported by owner and correct before
proceeding.
Boiler area
1. Verifythat boilerareais freeofanycombustiblematerials,
gasolineandotherammablevaporsandliquids.
2. Verifythat boiler area (and air intake)isfree of anyofthe
contaminants listed in Table 2 on page 5ofthismanual.Ifany
ofthesearepresentintheboilerintakeairvicinity,theymust
beremoved.Iftheycannotberemoved,installcombustionair
piping to the boiler in accordance with national, provincial or
local codes.
Air openings
1. Verify that combustion and ventilationair openings to the
boilerroomand/orbuildingareopenandunobstructed.Check
operationandwiringofautomaticcombustionairdampers,if
used.
2. Verifythatboilerventdischargeandairintakearecleanand
freeofobstructions.
Flue gas vent system
1. Visuallyinspectentireuegasventingsystemforblockage,
deteriorationorleakage.Repairanyjointsthatshowsignsof
leakageinaccordancewithventmanufacturer’sinstructions.
2. Verifythatmasonrychimneysarelined,liningisingoodcondi-
tion, and there are not openings into the chimney.
Failuretoinspectfortheaboveconditionsandhave
them repaired can result in severe personal injury
or death.
Pilot and main burner flames
1. Visually inspect pilot burner and main burner flames as di-
rected under Section 7, page 20ofthismanual.
Water piping
1. Checktheboilerinteriorpipingandallsystempipingforsigns
ofleaks.
2. Repairanyleaksbeforeproceeding.
Electricalshockhazard—Turnoffpowertotheboiler
beforeanyserviceoperationontheboilerexceptas
noted otherwise in this instruction manual. Failure
toturnoffelectricalpowercouldresultinelectrical
shock,causingseverepersonalinjuryordeath.
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to
boiler will occur, resulting in substantial property
damage.
Eliminateallsystemorboilerleaks.Continualfresh
makeupwaterwillreduceboilerlife.Mineralscan
buildupinsections,reducingheat transfer,over-
heatingcastiron,andcausingsectionfailure.Leak-
ing water may also cause severe property damage.
Boiler heating surfaces
1. Disconnect the vent pipe at the boiler inducer outlet connection
afterturningoffpowertotheboiler.
2. Useabrightlighttoinspecttheuepipeinteriorandinducer
interior.
3. Inspect theboilerventoutlet areaandheating surfacesby
lookingthroughtheopening.
4. Iftheventpipeorinducerinteriorshowevidenceofsoot,fol-
low“Cleaningboilerheatingsurfaces”,page 27, to remove
theuecollectorandcleantheboilerifnecessaryafterclose
inspectionofboilerheatingsurfaces.Ifthereisevidenceof
rustyscaledeposits,checkthewaterpipingandcontrolsystem
tomakesuretheboilerreturnwatertemperatureisproperly
maintained(perthismanual).
5. Reconnectventtoinduceroutlet(sealjointperpage 8)and
replaceallboilercomponentsbeforereturningtoservice.
6. Checkinsideandaroundboilerforevidenceofanyleaksfrom
theboiler.Iffound,locatesourceofleaksandrepair.
Burners and base
1. Afterturningoffpowertotheboiler,removethejacketdoor
andbaseaccesspanel(Figure 21, item 4, page 42).
2. Inspectburnersandallothercomponentsintheboilerbase.
3. Ifburnersmustbecleaned,raiserearofeachburnertorelease
fromsupportslot,slideforwardandremove.Thenbrushand
vacuumtheburnersthoroughly,makingsureallportsarefree
ofdebris.Carefullyreplaceallburners,makingsureburner
with pilot bracket is replaced in its originalposition and all
burnersareupright(portsup).
4. Inspectthebaseinsulation.
a. Verifythattheinsulationisintactandsecureagainstall
foursidesofthebase.
Ifinsulationisdamagedordisplaced,donotoper-
ate the boiler. Replace or reposition insulation as
necessary. Failure to replace damaged insulation
can result in a fire hazard, causing severe personal
injury, death or substantial property damage.
Condensate drain system
1. Ifventsystemisequippedwithacondensatedrain,checkthe
hoseandconnectionsfortightness.
2. Verifythehoseisunobstructedandingoodconditionandthat
condensatecanowfreely.Replacehoseifnecessary.