EasyManua.ls Logo

Williamson Series 2 - Page 9

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
Part Number 550-142-785/0812
Table 4 Maximum vent length
Max.vent length
(feet)
Total number of 90° elbows
(Notes 1 & 2)
1 2 3 4 5 6
GWI-047 to GWI-158
55 48 41 34 27 20
GWI-190
35 28 21 14 7 --
Notes:
1. Do not include termination fitting when counting total number of elbows.
2. One (1) 90° elbow is equivalent to two (2) 45° elbows.
GWI
Series 2 Gas-Fired Water Boilers – Boiler Manual
Direct exhaust venting
Obtain vent system components
1. ThefollowingspecialgasventsystemscomplywithUL-1738
andULC-S636standardsandarecertiedbyCSAastheonly
systemssuitableforusewithGWIboilers(all3”diameter):
• Heat-Fab,Inc.Saf-TVent
®
• Flex-LInternational,Inc.StaR-34
• Z-Flex
®
,Inc.Z-VentII
• ProTechSystemsFasNSeal™
Useonlytheventstarterofthesamemanufacturer
astheventcomponents.Donotmixcomponents
fromdifferentsystems.Theventsystemcouldfail,
causing flue gas spillage, resulting in severe per-
sonal injury or death.
2. Selectverticalorsidewallventingdependingonjobrequire-
ments.
3. RefertoTable4formaximumventrunlengthsandnumberof
elbows.DonotexceeddatainTable 4.
4. SelectventcomponentsfromseparateGWI Vent Component
Supplement.Allcomponents,includingtheventstarter,must
beofthesameventmanufacturer.Donotmixcomponents.
1. Select a vent pipe manufacturer from separate GWI Vent
Component Supplement and obtain all vent components
needed, based on boiler location and venting method.
2. Youmustusetheventstarter(seebelow)madebytheventpipe
manufacturer.SeeGWI Vent Component Supplementfor
partnumberofeachcomponent,listedbyventmanufacturer.
Useonlytheventstarterofthesamemanufacturer
astheventcomponents.Donotmixcomponents
fromdifferentsystems.Theventsystemcouldfail,
causing flue gas spillage, resulting in severe per-
sonal injury or death.
3. Follow all applicable national, state, local or provincial codes
whenventingtheGWIboiler.
4. Connectventstartertoblowerhousingoutletasshownbelow.
a. Donotmixcomponentsfromdifferentventmanufacturers.
b. Maintainminimum2”clearancefromcombustiblematerials
to vent pipe.
c. Seal with sealant specied byventpipe manufacturer,
using
3
/
8
bead(notrequiredforFasNSeal™).
d. Tighten strap at band clamp screw until strap is snug
around blower housing.
3 Vent installation continued