42 WILO SE 05/2016 V05 DIN A4
English OPERATION AND FUNCTION
4. Display of parameters currently set as well as data
for the switchgear (type, serial number etc.)
5. Basic settings for the switchgear
6. Fault memory
7. Service menu (can only be activated by Wilo
customer service)
The menu structure is adapted automatically
based on the signal transmitters used. Menu
1.2.2.0 is only visible for instance if a level sensor
is connected and activated accordingly in the
menu.
6.4.1. Menu structure
1. Start the menu by pressing the operating knob
for3sec.
2. Choosetheselectedmenu:EasyorExpert.
3. Follow the menu structure below for the desired
valueandchangethisaccordingtoyourspeci-
cations.
Menu 1: Control parameters
No. Description Display
1.1.0.0
Operating mode
1.1.1.0
Selection:
empty
 l l
1.2.0.0
Control values
1.2.2.0
Threshold for activation/deac-
tivation level (only available if a
level sensor is used)
1.2.2.1
Base-load pump on
Valuerange:0.09to12.45
Factorysetting:0.62
1.2.2.2
Base-load pump off
Valuerange:0.06to12.42
Factorysetting:0.37
1.2.2.3
Peak-load pump 1 on
Valuerange:0.09to12.45
Factorysetting:0.75
1.2.2.4
Peak-load pump 1 off
Valuerange:0.06to12.42
Factorysetting:0.50
1.2.2.5
Peak-load pump 2 on
Valuerange:0.09to12.45
Factorysetting:1.00
1.2.2.6
Peak-load pump 2 off
Valuerange:0.06to12.42
Factorysetting:0.75
1.2.2.7
Peak-load pump 3 on
Valuerange:0.09to12.45
Factorysetting:1.25
Menu 1: Control parameters
No. Description Display
1.2.2.8
Peak-load pump 3 off
Valuerange:0.06to12.42
Factorysetting:1.00
1.2.5.0
Delay times for activation and
deactivation of the pumps
1.2.5.1
Base-load pump stop delay
Valuerange:0to60
Factorysetting:5
1.2.5.2
Peak-load pump(s) activation
delay time
Valuerange:1to30
Factorysetting:3
1.2.5.3
Peak-load pump(s) stop delay
Valuerange:0to30
Factorysetting:1
1.2.5.4
Stop delay at dry-running level
Valuerange:0to10
Factorysetting:0
1.2.5.5
Activation delay time after dry
run
Valuerange:0to10
Factorysetting:1
1.2.5.6
System activation delay time
after power interruption
Valuerange:0to180
Factorysetting:0
Menu 2: Communication parameters
No. Description Display
2.0.0.0
Communication
2.1.0.0
Field bus
Values:None,Modbus,BACnet,
GSM
Factorysetting:None
Menu 3: Pump activation
No. Description Display
3.0.0.0
Pump activation
3.1.0.0
Switching automatic mode on/
off
Values:ON,OFF
Factorysetting:OFF
3.2.0.0.
Operating mode per pump
3.2.x.0
Selection of pump 1 ... 4