44 WILO SE 05/2016 V05 DIN A4
English OPERATION AND FUNCTION
Menu 5: Basic switchgear settings
No. Description Display
5.2.5.0
Priority when dry run and high
water signals are present simul-
taneously**
Values:DryRun,HighWater
Factorysetting:DryRun
5.2.6.0
Signal detection for level con-
trol**
Values:Floater,Sensor
Factorysetting:Sensor
5.4.0.0
Limit values
5.4.1.0
Dry run level
Valuerange*:0.01to12.39
Factorysetting:0.12
5.4.2.0
High water alarm level
Valuerange*:0.12to12.50
Factorysetting:1.50
5.4.4.0
High water alarm delay
Valuerange:0to30
Factorysetting:0
5.4.5.0
Running time monitoring of indi-
vidual pumps
Values:ON,OFF
Factorysetting:OFF
5.4.6.0
Max. running time of individual
pumps
Valuerange:0to60
Factorysetting:10
5.4.7.0
Behaviour in case of mains con-
nection errors**
Values:OFF,Message,Stop
Pumps
Factorysetting:StopPumps
5.4.8.0
Behaviour on activation of ther-
mal motor winding monitoring
and leakage detection**
Values:AutoReset,ManuReset
Factorysetting:AutoReset
5.4.9.0
Behaviour when “External OFF”
contact is open**
Values:Ext.Off,Alarm
Factorysetting:Ext.off
5.5.0.0
Setting for signal outputs
5.5.1.0
Collective run signal (SBM)**
function
Values:Ready,Run
Factorysetting:Run
5.5.2.0
Collective fault signal function**
Values:Fall,Raise
Factorysetting:Raise
5.6.0.0
Pump cycling**
Menu 5: Basic switchgear settings
No. Description Display
5.6.1.0
General pump cycling
Values:ON,OFF
Factorysetting:ON
5.6.2.0
Pump cycling after time interval
Values:ON,OFF
Factorysetting:OFF
5.6.3.0
Running time of base-load pump
until pump cycling
Valuerange:0to60
Factorysetting:10
5.7.0.0
Pump kick**
5.7.1.0
Switching pump kick on/off
Values:ON,OFF
Factorysetting:OFF
5.7.2.0
Interval between pump kicks
Valuerange:1to336
Factorysetting:12
5.7.4.0
Running time of pump(s) on
pump kick
Valuerange:1to30
Factorysetting:5
* The value range is dependent on the sensor
measuring range.
** See the function description below
6.4.2. Explanation of individual functions and settings
Menu 5.1.3.0 / GSM
This menu item is only active if the optionally
available module has been installed in the switch-
gear. Please contact Wilo customer service for
moreinformationandforretrotting.
Menu 5.2.5.0 / Priority when dry run and high
water signals are present simultaneously
If the system malfunctions, it may happen that
both signals are present at the same time. In such
cases, it is necessary to stipulate which signal is
overriding:
• “Dry Run” Dry-running protection
• “HighWater”:Highwateralarm
Menu 5.2.6.0/ Signal detection for level control
The switchgear can be operated for level meas-
urementbothwithoatswitchesandwithalevel
sensor.Thefollowingoptionsareavailable:
• “Floater”:Floatswitch
• “Sensor”:Levelsensor
Ifoatswitchesareused,someofthemenu
items will not be available!
Menu 5.4.7.0 / Behaviour in case of mains con-
nection errors**
This function can only be used with a 3~-mains
connection. With a 1~-mains connection, this