English OPERATION AND FUNCTION
Menu 5: Basic switchgear settings
No. Description Display
5.2.5.0
Priority when dry run and high
water signals are present simul-
taneously**
Values:DryRun,HighWater
Factorysetting:DryRun
5.2.6.0
Signal detection for level con-
trol**
Values:Floater,Sensor
Factorysetting:Sensor
5.4.0.0
Limit values
5.4.1.0
Dry run level
Valuerange*:0.01to12.39
Factorysetting:0.12
5.4.2.0
High water alarm level
Valuerange*:0.12to12.50
Factorysetting:1.50
5.4.4.0
High water alarm delay
Valuerange:0to30
Factorysetting:0
5.4.5.0
Running time monitoring of indi-
vidual pumps
Values:ON,OFF
Factorysetting:OFF
5.4.6.0
Max. running time of individual
pumps
Valuerange:0to60
Factorysetting:10
5.4.7.0
Behaviour in case of mains con-
nection errors**
Values:OFF,Message,Stop
Pumps
Factorysetting:StopPumps
5.4.8.0
Behaviour on activation of ther-
mal motor winding monitoring
and leakage detection**
Values:AutoReset,ManuReset
Factorysetting:AutoReset
5.4.9.0
Behaviour when “External OFF”
contact is open**
Values:Ext.Off,Alarm
Factorysetting:Ext.off
5.5.0.0
Setting for signal outputs
5.5.1.0
Collective run signal (SBM)**
function
Values:Ready,Run
Factorysetting:Run
5.5.2.0
Collective fault signal function**
Values:Fall,Raise
Factorysetting:Raise
5.6.0.0
Pump cycling**
Menu 5: Basic switchgear settings
No. Description Display
5.6.1.0
General pump cycling
Values:ON,OFF
Factorysetting:ON
5.6.2.0
Pump cycling after time interval
Values:ON,OFF
Factorysetting:OFF
5.6.3.0
Running time of base-load pump
until pump cycling
Valuerange:0to60
Factorysetting:10
5.7.0.0
Pump kick**
5.7.1.0
Switching pump kick on/off
Values:ON,OFF
Factorysetting:OFF
5.7.2.0
Interval between pump kicks
Valuerange:1to336
Factorysetting:12
5.7.4.0
Running time of pump(s) on
pump kick
Valuerange:1to30
Factorysetting:5
* The value range is dependent on the sensor
measuring range.
** See the function description below
6.4.2. Explanation of individual functions and settings
Menu 5.1.3.0 / GSM
This menu item is only active if the optionally
available module has been installed in the switch-
gear. Please contact Wilo customer service for
moreinformationandforretrotting.
Menu 5.2.5.0 / Priority when dry run and high
water signals are present simultaneously
If the system malfunctions, it may happen that
both signals are present at the same time. In such
cases, it is necessary to stipulate which signal is
overriding:
“Dry Run” Dry-running protection
“HighWater”:Highwateralarm
Menu 5.2.6.0/ Signal detection for level control
The switchgear can be operated for level meas-
urementbothwithoatswitchesandwithalevel
sensor.Thefollowingoptionsareavailable:
“Floater”:Floatswitch
“Sensor”:Levelsensor
Ifoatswitchesareused,someofthemenu
items will not be available!
Menu 5.4.7.0 / Behaviour in case of mains con-
nection errors**
This function can only be used with a 3~-mains
connection. With a 1~-mains connection, this

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Control SC-L and is the answer not in the manual?

Wilo Control SC-L Specifications

General IconGeneral
BrandWilo
ModelControl SC-L
CategoryControl Unit
LanguageEnglish

Related product manuals