30 Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09
7.2.1.3 Control settings -> Control menu
Fig.27: Settings→Control menu item
Parameters and functions that have an impact on the control.
Fig.28: Settings→Control→Control mode
menu item
The control modes p-c and p-v can be set.
With the p-c control mode, automatic control is based on the deviation between actual and
nominal pressure.
With the p-v control mode, the energy consumption is also taken into account.
Fig.29: Settings→Control→PID menu item
In speed-controlled systems, a PID controller is used for control.
The P and I shares can be adjusted according to local conditions.
The D share is adjustable, but should be left at 0.0s.
Fig.30: Settings→Control→BLP selection
scheme menu item
With the p-v control mode, the “Synchro” scheme is used.
With the p-c control mode, you can choose between “Vario” and “Cascade”.
“Vario” offers better control quality compared to “Cascade”.
7.2.1.4 Control settings -> Monitoring
functions menu
Fig.31: Settings→Monitoring settings menu
item
The monitoring functions ensure the operation of the units in the approved range.