Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09 35
Fig.52: Settings→Additional settings→Tube
filling function 2/2 menu item
If the current pressure is below the set start pressure, the tube filling function is activated.
The system operates in this state until the pressure exceeds the above level again or the
maximum running time (adjustable) of the pipe filling is reached.
After that, the controller operates in automatic mode.
Fig.53: Settings→Additional settings→Stag-
nation menu item
Stagnation monitoring is available in the p-v control mode.
If the function is active, it is checked that at least the specified amount of water is pumped
through the unit within 3 days.
If the specified quantity is not conveyed by the unit, a stagnation warning is generated.
This does not affect the operation of the unit.
7.2.2 Interaction / Communication menu
7.2.2.1 Interaction / Communication ->
Alarms menu
Fig.54: Communication -> Alarms menu item
The menu contains the overview of current and previous alarms and warnings of the system.