6.3 Setting the temperature control
NOTICE: If the pump is running during a
switch-on time, “1/on”, “2/on” or “3/on” is
shown in the display.
During the switch-off time, “off” is shown in the
display.
1.
2. Select temperature control
(flashes).
+
3. Set the temperature.
Setting range = 40 70 °C.
Means that the temperature
control is switched off.
The pump runs on, independent
of the return temperature.
+
Warns about a non DVGW-compliant setting and
appears when the temperature is below 55 °C.
4. Switching thermal disinfection
on/off.
+
5. Select the standard display.
+
65 °C
no °C
AA1