28 WILO SE 05/2017
Once power returns after a power interruption, the pump goes back into operation with
different start-up times, depending on the setting chosen. See chapter 10.2 for the
restart times.
SSM: Faults always result in the activation of the collective fault signal (“SSM” via a relay).
The contact of the collective fault signal (potential-free normally closed contact) can be
connected to a building automation system. The internal contact is closed if the pump is
without power, if there is no fault or if there is a malfunction of the control module. The
performance of the SSM is described in chapters 7.2.2 and 10.1.
7 Installation and electrical connection
DANGER! Risk of fatal injury!
Incorrect installation and improper electrical connections can be life-threatening.
Danger from electrical current must be eliminated.
The installation and electrical connection may only be carried out by qualified person-
nel in accordance with the applicable regulations!
Adhere to regulations for accident prevention!
Comply with the regulations of the local energy supply company!
CAUTION! Risk of property damage!
Excessive force on the control module of the pump is to be avoided.
The mains and control cable of the Yonos ECO BMS series can only be connected at the
factory. Subsequent installation is not possible.
Never pull on the pump cable!
•Do not kink the cable!
Do not place any objects on the cable!
7.1 Installation
WARNING! Risk of injury!
Incorrect installation can result in personal injury.
There is a crushing hazard!
There is a risk of injury due to sharp edges/burrs. Wear appropriate protective clothing
(e.g. safety gloves)!
There is a risk of injury hazard due to the pump/motor falling!
Use suitable lifting gear to secure the pump/motor against falling!
CAUTION! Risk of property damage!
Incorrect installation can result in property damage.
Only use qualified personnel for installation work!
Observe national and regional regulations!
When the pump needs to be transported, it may be carried only by the motor/pump
housing.
Never by the control module or preinstalled cable!
Installation within a building:
Install the pump in a dry, well-ventilated room. Ambient temperatures below -10°C are
not permitted.
Installation outside a building (outdoor installation):
Install the pump in a chamber (e.g. light well, ring chamber) with a cover or in a cabinet/
housing as weather protection.
Avoid exposure of the pump to direct sunlight.
Protect the pump against rain.