12
5 Flue systems
To ensure safe and proper use, this air heater must be
connected to a flue system. This flue system must be
installed according to this manual as well as national and
local regulations. A flue system consists of a flue terminal,
piping and an optional condensate discharge system.
CAUTION! Do not use flue terminals for condensing
appliances on non-condensing heaters. This can lead to
water inside the flue system.
NOTICE Only use the prescribed flue material for the
roof terminal, wall terminal and for the piping between
the heater and the terminal. This is the only way the
installation will be approved.
NOTICE Local regulations can require the flue terminal to
be placed at least 0,6 m above roof level.
NOTICE Local regulations can require a minimum
distance between the flue terminal and air ventilation
openings on the building.
5.1 Flue terminals
The following flue terminals are compatible with this air
heater:
Vertical discharge
Flue terminal Art. Nr.
DDV130/200 IA8305
Horizontal discharge
Flue terminal Art. Nr.
CT130/200 IA8312
955
1850
200O
H.O.H. 225
Ø 130
Ø 130
Flexible O130
Figure 11 - Vertical flue terminal
O200
O130
Ho
H 225
600
m
ax. 300
180
Flexible O 130
Figure 12 - Horizontal flue terminal