3 Version
3.1 Technical Information
CWL -2-325
Supply voltage [V/Hz] 230V/50Hz
Dimensions (w x h x d) [mm]
4-0 Version 2-2 Version
750 x 650 x 560 750 x710 x 560
Duct diameter [mm] ø160
Ext. diameter condensate discharge [mm] ø32
Weight [kg] 37
Filter class ISO Coarse 60% (ISO ePM1.0 50% for the air supply optional)
Fan setting (factory setting) 0 1 2 3 max
Factory setting [m³/h] 50 100 150 250 325
Permissible resistance of duct system [Pa]2 5 9 19 21 43 59 118 100 200
Rated power (excl. preheater) [W] 6.1 6.4 8.2 9.7 15.4 19.4 46.9 61.4 87.2 116.5
Rated current (excl. preheater) [A] 0.08 0.08 0.09 0.11 0.16 0.19 0.42 0.53 0.73 0.94
Max. rated current (incl. preheater
switched on) [A]
6
Cos j
0.341 0.343 0.389 0.394 0.430 0.439 0.492 0.507 0.521 0.542
Sound power
Ventilation capacity [m
3
/h]
100 150 150 200 200 250 325
Sound power level Lw(A)
Static pressure [Pa] 25 25 50 50 100 150 150
Casing radiation [dB(A)] 27 34 35 40 41 46 51
Duct “From dwelling’ [db(A)] 32 40 38 46 44 49 55
Duct ‘To dwelling’ [db(A)] 44 49 51 55 57 62 69
*) Duct noise including end correction
In practice the value may differ by 1dB(A) through measurement tolerances.
Resistance
of duct
system [Pa]
Note:
The stated
value in the
circle is the
capacity (in
Watt) per fan.
Flow rate [m
3
/h]
Version