Step
No
Description Factory settings Setting range Comment
4.3 Filter reset No Yes / No
5
External heater
5.1 Preheater on and off Off On / Off
5.2 Postheater on and off Off On / Off
5.3 Temperature postheater 21 °C 15 °C / 30 °C
6
CO
2
sensor
6.1 Switching eBus CO
2
sensor off
and on
Off On / Off
6.2
Min. PPM eBus CO
2
sensor 1
400 PPM
400 - 2000 PPM
6.3
Max. PPM eBus CO
2
sensor 1
1200 PPM
6.4
Min. PPM eBus CO
2
sensor 2
400 PPM
6.5
Max. PPM eBus CO
2
sensor 2
1200 PPM
6.6
Min. PPM eBus CO
2
sensor 3
400 PPM
6.7
Max. PPM eBus CO
2
sensor 3
1200 PPM
6.8
Min. PPM eBus CO
2
sensor 4
400 PPM
6.9
Max. PPM eBus CO
2
sensor 4
1200 PPM
7 Humidity sensor
7.1 Switching humidity sensor on
and off
Off On / Off
7.2 Sensitivity of humidity sensor 0 +2 = most sensitive
0 = basic setting
-2 = least sensitive
8 Cascade
8.1 Appliance setting 0 (Master) 0 / 9
(0=Master; 1 t/m 9 = Slave 1 t/m Slave
9)
12 Central heating + heat recovery
12.1 Status Off On / Off
14 Communication
14.1 Type of Bus connection ModBus Off / ModBus/ externalBus
14.2 Slave address 20 1 - 247 For Modbus
14.3 Baudrate 19k2 1200 / 2400 / 4800 / 9600 / 19k2 /
38k4 / 56k / 115k2
For Modbus
14.4 Parity Even No / Even / Odd For Modbus
15 Appliance settings
Setting values
xxxx
7100833_202010 WOLF GmbH | 47