13 Setting values
13.1 Setting values standard appliance
The below setting values are for a CWL -2-400-appliance without Plus pcb.
Step
No
Description Factory settings Setting range Comment
1 Flow rate
1.1 Air flow rate setting 0 50 m³/h 0 or adjustable between 50 m³/h and
400 m³/h (never higher than step no.
1.2)
1.2 Air flow rate setting 1 100 m³/h Adjustable between 50 m³/h and 400
m³/h (not higher than step no. 1.3 or
lower than step no. 1.1)
1.3 Air flow rate setting 2 200 m³/h Adjustable between 50 m³/h and 400
m³/h (not higher than step no. 1.4 or
lower than step no. 1.2)
1.4 Air flow rate setting 3 300 m³/h Adjustable between 50 m³/h and 400
m³/h (not lower than step no. 1.3)
1.5 Imbalance permissible Yes Yes / No
1.6 Imbalance (Open fireplace) 0% 0% / +20%
1.7 Offset supply 0% -15% / +15% fan setting
Value calculated
back to set flow
rate, see screen
1.8 Offset exhaust 0% -15% / +15% fan setting
1:19 Default fan setting 1 0 or 1
2 Bypass
2.1 Mode Bypass Automatic - Automatic
- Bypass closed
- Bypass open
2.2 Bypass temperature "from
dwelling"
24 °C 15 °C / 35 °C
2.3 Bypass temperature “from
outside”
10°C 7 °C / 15 °C
2.4 Bypass hysteresis
2 °C 0 °C / 5 °C
2.5 Mode Bypass boost
Off On / Off
2.6 Fan setting selection Bypass
boost
3 0 / 3
3 Frost protection
3.1 Frost temperature 0 °C -1,5 °C /1,5 °C
3.2 Minimum intake temperature 10 °C 7 °C /22 °C
4 Filter message
4.1 Number of days until filter
message
90 1 / 365 days
4.2 Start of filter wizard No Yes / No
Setting values
46 | WOLF GmbH 7100833_202010