Clearances
Clearances for LH ceiling unit or wall
unit in metres
LH LH to LH LH to wall
25 7 - 9 3 - 4
40 9 - 11 3 - 5
63 11 - 13 4 - 6
100 13 - 15 5 - 7
Discharge accessories
referring to a.m. spacing, a ∆t air (= t discharge - t room) of approx. 25K and high
speed.
LH 25 40 63 100
Spacing:
Discharge/Floor
up to 2,5 m 4-side-discharge 4-side-discharge 4-side-discharge 4-side-discharge
3-4 m Wide spread
discharge
Wide spread
discharge
Wide spread
discharge
Wide spread
discharge
4-5 m Cone Cone Louvre Wide spread
5-6 m Cone Cone Cone Louvre
à partir de 6 m Cone Cone Cone Cone
If the temperature difference ∆t air exceeds 30K the above selection table is no longer
applicable, because of the reduced penetration.
Prior to the Installation
7-15m 7-15m 3-7m
Air throw
Spacing Spacing Spacing
Primary air Primary air
Larger throw for very
high rooms by means of
discharge cone
Four-side discharge for lower rooms
Secondary
vortex
Secondary
vortex
Primary air
larger throw
by approx. 25%
up to 2,5 m max.