42
Technical information
Technical information
Output data at +7/35º and +7/45º are stated according to the European standard EN 14511.
1)
aM type fuse, D characteristic MCB. Both units require a means of electrical isolation.
2)
Dimensions excl. feet, supplied min 20 mm - max 30 mm depending on adjustment.
Greensource Hot water distribution unit
Control unit Rego 800
Output electric element kW 4,5
Output circulation pump kW 0,2
Electrical supply 230V 1N~
Max. power consumption kW 4,7
Fuse size
1)
AT 25
Max working pressure bar (MPa) 2.5 (0.25)
DHW volume l 151
CH Buffer volume l 55
Expansion tank l 12
Overheat protection ºC 90
Min. fl ow heating system l/s 0
Pump for heating system G1 Wilo Star RS 25/6-3
Heat carrier pump G2 Wilo Star RS 25/6-3
Dimensions (WxDxH) mm 600/615/1660
Weight, excluding water kg 122
Weight, including water kg 347
Greensource 6 kW 7 kW 9.5 kW
Emitted/Supplied output at +7/35º kW 5,5 / 1,5 7,1 / 2,1 8,8 / 2,3
Emitted/Supplied output at +7/45º kW 5,1 / 1,7 6,9 / 2,5 8,5 / 2,8
Heat carrier fl ow nominal l/s 0,19 0,29 0,34
Internal pressure drop heat carrier kPa 5 6 7
Air fl ow m³/h 2200 2200 2200
Electrical consumption fan A 0,44 0,44 0,44
Electrical supply 230V 1N~
Fuse size
1)
AT 16 25 25
Compressor Scroll
Highest outgoing heat carrier temperature ºC 65 65 65
Refrigerant fi lling R-407C kg 2 2,3 2,4
HTF connection, clamping ring mm Hose 1 inch internal thread
Defrost system Hot gas with four-way valve
Operating temperature °C -20 – +35
Dimensions (WxDxH)
2)
mm 820x640x1190
Weight kg 140 145 155
Outer casing Galvanised enamelled plate