44
Manufacturer
Appliance: IVT Industrier AB, part of Bosch Thermotechnik GmbH
Box 1012, SE-57343 Tranås, Sweden
Cylinder: BoRö Pannan AB
Bangårdsv. 1, SE-95231 Kalix, Sweden
Supplementary technical information
Maximum water supply pressure to the pressure reducing valve 16 bar
Operating pressure DHW 3 bar
Expansion vessel charge pressure 3 bar
Expansion valve setting 6 bar
Maximum primary working pressure 2,5 bar
Set opening pressure of the combined temperature and pressure relief valve 7 bar / 95°C
Expansion vessel, 19 Litres 3 bar
Cylinder reheat times, Inner cylinder 151 Litres of DHW
Full volume heat-up from 15°C to 55°C with a primary fl ow temperature of 60°C takes 2 hours and 15 minutes
Full volume re-heat to 55°C after 70% of the cylinders contents were drawn off takes 1 hour and 50 minutes
Important note
Only genuine Bosch Thermotechnology spare parts can be used with these products.