EasyManua.ls Logo

Xantrex 3000

Xantrex 3000
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Battery Types
B–8 975-0128-01-01
Battery
Connections
Connections to battery posts must be made with permanent connectors
that provide a reliable, low-resistance connection. Do not use alligator
clips. Clean the connections regularly and prevent corrosion by using a
protective spray coating or Vaseline.
Battery State of
Charge
You can measure battery state of charge with a hydrometer or
approximate state of charge with a voltmeter. Use a digital voltmeter that
can display tenths or hundredths of a volt when measuring 10 to 30 volts.
Make your measurements when the battery has not been charged or
discharged for several hours. For a deep-cycle battery at 77º F (25º C), use
the following table:
Battery Voltage State of Charge
12.7–13.0 V 100%
12.5–12.6 V 80%
12.3–12.4 V 60%
12.1–12.2 V 40%
11.9–12.0 V 20%
XPower3000.book Page 8 Wednesday, December 10, 2003 6:52 AM